CABLING SCHEDULE
Building C — the BBQ & store
The rear outbuilding. The rear outbuilding — a barbecue and entertaining area, plus an enclosed store room. This sheet covers Building C’s own cabling and devices. The store room is also the site’s server room; that has its own two sheets.
24 STEET ST
FOOTSCRAY
FOOTSCRAY
NBN
Carrier lead‑in from the street to the NTD in this room — roughly 36.6 m, the full depth of the block. Position confirmed by NBN, not by us.
F‑01
Fibre to Building A (the main dwelling — ground-floor passage cabinet) — ~8.5 m wall to wall, order 18–22 m. OS2 single‑mode, LC/UPC both ends.
P‑02
13 × Cat6A to Building B (the second small home) — ~4.5 m wall to wall, allow 10–15 m per cable, run underneath.
ITEM — BUILDING C’S OWN DEVICES
POINTS
places to cable to
places to cable to
CABLES
to pull
to pull
LABEL
TERMINATES AT
Data outlet
BBQ kitchen ⋅ store room
2
2
Cat6A ⋅ 1 each
C-01-001, 002
Patch panel → switch
Wi‑Fi access point
UniFi U7 Pro ⋅ under the BBQ roof — covers the entertaining area and spills into the yard
1
1
Cat6A
C-AP-01
Patch panel → switch (PoE)
Camera
UniFi G6 Turret — position 7, plus one covering the server‑room door
2
2
Cat6A ⋅ 1 each
C-CAM-01, 02
Patch panel → switch (PoE)
Entry reader — server room
UniFi UA‑G2 keypad. Gives a timestamped log of who entered the room holding the gateway and all the footage.
1
1
Cat6A
C-DR-RDR
Patch panel → hub reader port
Exit sensor + door position sensor
Exit sensor above the door (so leaving doesn’t read as a break‑in) ⋅ magnetic contact on the frame (open or shut) — two fittings, one shared cable
2
2
2-core ⋅ 1 each
C-DR-REX
Terminal strip → hub
Electric strike
In the server‑room door frame ⋅ supplied and fitted by the cabler
1
1
2-core power
C-DR-LCK
Terminal strip → hub lock output
9
points in Building C
10
of its own cables to pull
23
cables terminate here in total — C’s 10 plus B’s 13
17 / 6
on the patch panel / on the terminal strip
THE SERVER ROOM
The head‑end gear has its own two sheets. “The server room” has the rack, unit by unit, and everything that lands in it. “What goes in the server room” is the ordering list. This sheet is Building C’s own cabling only.
Equipment around Building C
Fitted in the BBQ area and on the building itself.
ITEM
SUGGESTED PRODUCT
QTY
WHERE IT GOES
Wall plates + keystones
Cat6A, 2 jacks per plate
2 / 4
BBQ kitchen, store room
Wi‑Fi access point
UniFi U7 Pro
1
Ceiling under the BBQ roof — sheltered, not exposed
Camera
UniFi G6 Turret
2
Position 7 + the server‑room door
Entry reader
UniFi UA‑G2 keypad
1
Outside the server‑room door
Exit sensor
PIR request‑to‑exit
1
Inside, above the door
Door position sensor
Magnetic reed contact — switch on the frame, magnet on the leaf
1
Tells the system whether the door is open or shut — door‑ajar alerts, and forced‑door detection
Electric strike
Cabler‑supplied — matched to the door type
1
In the server‑room door frame