24 Steet StreetFOOTSCRAY · NETWORK
EQUIPMENT LIST ⋅ BUILDING C
What goes in the server room
Every part in the head‑end, in one list. This is the ordering sheet — the rack elevation and what lands in the room are on the server room sheet.
24 STEET ST
FOOTSCRAY
Nothing here has been quoted yet. The one SFP+ figure sits on Building A’s list, and that 2‑pack covers both ends of the fibre — do not buy a second pack for this room.
ITEM
PRODUCT / SPEC
QTY
PRICE AUD
NOTES
ACTIVE NETWORK
Gateway + recorder
UniFi Dream Machine Pro Max
1
— quote
1U. Routes the whole site, runs the controller, records the cameras. One box instead of three
Surveillance drives
WD Purple or Seagate SkyHawk, 8 TB
2
— quote
Mirrored — 8 TB usable, not 16. 12 camera streams site‑wide. Record the doorbell on motion
Core switch
UniFi USW‑Pro‑48‑PoE
1
— quote
~17 of 48 ports. Carries C’s devices and all of Building B’s. 4 × SFP+
SFP+ transceiver
UniFi UACC‑OM‑SM‑10G‑D‑2 — duplex LC UPC
1
shared
Covered by the 2‑pack on Building A’s list ($169.01, verified 13 Aug 2026). One module each end of F‑01 — buy once
SFP+ DAC lead
10G SFP+ direct‑attach, 0.5–1 m
1
— quote
Gateway to switch, box to box inside the cabinet. Never touches the patch panel
Fibre patch lead
LC/UPC to LC/UPC, single‑mode duplex
1
— quote
FOBOT to switch. UPC, not APC
DOOR ACCESS
Access hub
UniFi EAH‑8
1
— quote
Drives C’s server‑room door and Building B’s entry. 2 of 8 used. Mains powered
Hub battery
Sealed lead‑acid, 32–48 V
1
— quote
Keeps Building B’s front door working through a power cut here. B has no hub of its own
Terminal strip
DIN‑rail terminal blocks, ~16 way
1 set
— quote
Two doors’ low voltage — C’s and B’s — land here, then jumper to the hub
TERMINATION — where field cable stops
Patch panel
Cat6A, 24 port keystone
1
— quote
18 of 24 used — C’s 9 plus Building B’s
Fibre enclosure (FOBOT)
1U, LC/UPC adaptor plate
1
— quote
F‑01 out to Building A lands here and never moves again
Patch leads
Cat6A stranded, factory‑made
~24
— quote
Assorted short lengths. Never solid‑core as a patch lead
Cable management
1U brush or finger bar
3
— quote
Between panel, switch, gateway and FOBOT
POWER
UPS
~1000 VA
1
— quote
Covers Building B too — B has no UPS of its own, so a cut here takes B’s network and its door controller with it
Rack PDU
1U, 6–8 outlet
1
— quote
Fed from the UPS
Surge protection
On the carrier lead‑in and the copper run to B
1 set
— quote
Any copper leaving a building needs it. The fibre to Building A does not
Dedicated circuit + GPOs
Electrician — not a network item
1
— quote
Dedicated circuit required. Raise it early
THE ROOM ITSELF
Cabinet
15U, lockable, ≥450 mm deep
1
— quote
Measure the store room before ordering. The whole outbuilding is ~17.7 m²
Ventilation / fan kit
Thermostatic cabinet fan, or room vents
1
— quote
A closed brick room next to a barbecue will cook this gear. Vent to outside, not into the cooking area
Shelves
Cantilever
2
— quote
One for the NTD and hub, one for the battery
Earth & bonding kit
Cabinet bonding strap + lug
1
— quote
Per AS/CA S009
Labels
Label printer + cassettes
1 set
— quote
Every cable both ends, plus the panel and the strip
NTD
Supplied and installed by nbn
1
n/a
Not ours to buy. Position confirmed by nbn, not by us — the lead‑in runs the full ~36.6 m depth of the block
15U
cabinet height
23
line items
0
priced here
2
buildings depend on this room
What this room carries for other buildings
C is not just its own head-end. Two other buildings lean on it.
WHAT
WHY IT DEPENDS ON THIS ROOM
SCALE
Building B — every port
B has no switch. All 13 of its cables terminate on C’s patch panel
13 cables
Building B — its front door
C’s hub drives B’s reader, strike and sensors
1 door
Building B — its power backstop
C’s UPS and hub battery are B’s only protection
no local UPS
Building B — its doorbell
The gate intercom at Building A reaches B’s screen through this room
via F‑01
Building A — its internet
A’s switch uplinks here over the fibre
1 fibre
← PREVIOUSThe server room